Please use this identifier to cite or link to this item: http://dspace.aiub.edu:8080/jspui/handle/123456789/1998
Full metadata record
DC FieldValueLanguage
dc.contributor.authorHazari, Md. Rifat-
dc.contributor.authorJahan, Effat-
dc.contributor.authorMannan, Mohammad Abdul-
dc.contributor.authorDas, Narottam-
dc.date.accessioned2024-01-16T10:19:03Z-
dc.date.available2024-01-16T10:19:03Z-
dc.date.issued2021-10-
dc.identifier.citationMd. Rifat Hazari, Effat Jahan, Mohammad Abdul Mannan, and Narottam Das, “Transient Stability Enhancement of a Grid-Connected Large-Scale PV System Using Fuzzy Logic Controller,” Electronics (MDPI Journal); Vol. 10, Issue 19, October 2021.en_US
dc.identifier.issn2079-9292-
dc.identifier.urihttp://dspace.aiub.edu:8080/jspui/handle/123456789/1998-
dc.description.abstractThis paper presents a new intelligent control strategy to augment the low-voltage ride-through (LVRT) potential of photovoltaic (PV) plants, and the transient stability of a complete grid system. Modern grid codes demand that a PV plant should be connected to the main power system during network disturbance, providing voltage support. Therefore, in this paper, a novel fuzzy logic controller (FLC) using the controlled cascaded strategy is proposed for the grid side converter (GSC) of a PV plant to guarantee voltage recovery. The proposed FLC offers variable gains based upon the system requirements, which can inject a useful amount of reactive power after a severe network disturbance. Therefore, the terminal voltage dip will be low, restoring its pre-fault value and resuming its operation quickly. To make it realistic, the PV system is linked to the well-known IEEE nine bus system. Comparative analysis is shown using power system computer-aided design/electromagnetic transients including DC (PSCAD/EMTDC) software between the conventional proportional–integral (PI) controller-based cascaded strategy and the proposed control strategy to authenticate the usefulness of the proposed strategy. The comparative simulation results indicate that the transient stability and the LVRT capability of a grid-tied PV system can be augmented against severe fault using the proposed FLC-based cascaded GSC controller.en_US
dc.language.isoenen_US
dc.publisherMDPIen_US
dc.subjectFuzzy logic controller (FLC); grid side converter (GSC); low-voltage ride-through (LVRT)en_US
dc.subjectPhotovoltaic (PV) system; transient stabilityen_US
dc.titleTransient Stability Enhancement of a Grid-Connected Large-Scale PV System Using Fuzzy Logic Controlleren_US
dc.typeArticleen_US
Appears in Collections:Publications From Faculty of Engineering

Files in This Item:
File Description SizeFormat 
79J_Dr Rifat_2021_Electronics_2.pdf180.06 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.